Please use this identifier to cite or link to this item: https://hdl.handle.net/10316/37034
Title: Eficiência energética em complexos de piscinas interiores
Other Titles: Energy efficiency in indoor swimming pools
Authors: Fernandes, Emanuel da Silva Lopes 
Orientador: Gaspar, Adélio Manuel Rodrigues
Keywords: Eficiência energética; Piscina coberta
Issue Date: Sep-2016
Abstract: Os complexos desportivos são em geral grandes consumidores de energia, em particular os que têm piscinas interiores. Em Portugal a gestão deste tipo de edifícios pertence na sua maioria às câmaras municipais. Estando estas fortemente condicionadas em termos dos gastos financeiros, importa melhorar a eficiência energética deste tipo de complexos, de modo a diminuir os consumos e os custos associados. Nesta dissertação é estudado o Complexo Olímpico de Piscinas Municipais de Coimbra, considerado um dos maiores e melhores complexos em Portugal. São analisados os consumos de eletricidade, gás natural e água e os seus respetivos custos. São calculados indicadores para comparação com valores de referência em guias de boas práticas. São também apresentados os resultados obtidos das medições efetuadas no sistema de AVAC, para estudar as temperaturas nas superfícies da bomba de calor desumidificadora e a potência elétrica consumida. Como as perdas térmicas por evaporação são consideráveis é efetuado um estudo aprofundado para as temperaturas reais registadas durante o ano de 2015, por comparação com as temperaturas de projeto. Conclui-se que há um potencial de poupança superior a 40 % na energia térmica usada para aquecer a piscina, com um controlo mais apertado e criterioso das condições ambientais da nave e da temperatura da água das piscinas.
Sport complexes are in general great energy consumers, in particular those with indoor swimming pools. In Portugal most of these swimming pools are municipal buildings that are managed with public money, what makes even more important to study energy efficiency in this cases. In this thesis is studied the Olympic Complex of swimming pools of Coimbra, which is one of the best and biggest complexes in Portugal. Electricity, natural gas and water consumptions and respective costs are analyzed and indicators are obtained for comparative purpose with reference values available in Guides of good practices. In this study are also presented the results of measurements done in the HVAC system to study the thermal conditions and is electric power input. The evaporation rate was calculated with both the real conditions and the design conditions and was concluded that by changing the set point values to the design conditions could be save up to 40 % in the energy losses by the pool.
Description: Dissertação de Mestrado em Engenharia Mecânica na especialidade de Energia e Ambiente, apresentada à Faculdade de Ciências e Tecnologia da Universidade de Coimbra.
URI: https://hdl.handle.net/10316/37034
Rights: openAccess
Appears in Collections:UC - Dissertações de Mestrado
FCTUC Eng.Mecânica - Teses de Mestrado

Files in This Item:
File Description SizeFormat
tese_versão 6 - final e correções.pdf2.56 MBAdobe PDFView/Open
Show full item record

Page view(s)

391
checked on Oct 29, 2024

Download(s) 50

1,066
checked on Oct 29, 2024

Google ScholarTM

Check


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.