Title: | Conforto térmico: Estudo paramétrico | Authors: | Forno, Ana Paula Borges do | Orientador: | Santos, Paulo Fernando Antunes dos Gervásio, Helena Maria dos Santos |
Keywords: | Conforto térmico; índices de conforto térmico; PMV; PPD; estudo paramétrico; método de Fanger; ASHRAE-55; EN 15251; thermal comfort; thermal comfort indices; PMV; PPD; parametric study; Fanger method; ASHRAE-55; EN 15251 | Issue Date: | Jul-2016 | metadata.degois.publication.location: | Coimbra | Abstract: | Devido ao aumento da qualidade de vida, principalmente nos países desenvolvidos, o conforto térmico tem vindo a requerer uma preocupação crescente ao longo dos anos, nomeadamente ao nível de estudos de eficiência energética, com vista à diminuição do consumo de energia, sem baixar o nível de conforto dos ocupantes. Assim, o nível de conforto térmico é um direito dos cidadãos, permitindo o alcance de um bem-estar ao nível da saúde e produtividade.
O conforto térmico no interior de edifícios depende de diversos parâmetros incluindo, o nível metabólico, o vestuário, a temperatura do ar, a temperatura radiante, a velocidade do ar e a pressão de vapor de água.
Nesta dissertação estudou-se a sensibilidade dos índices de conforto térmico PMV-PPD, através de um estudo paramétrico relativo aos parâmetros que influenciam o conforto térmico, referidos anteriormente. O estudo foi efetuado através de uma folha de cálculo que tem por base a metodologia desenvolvida por Fanger e proposta na norma ISO 7730, assim como um software desenvolvido nos EUA que permite efetuar uma comparação entra a norma ASHRAE-55 e a norma EN -15251.
Tendo em conta os resultados obtidos, pode-se verificar que parâmetros como, a velocidade do ar e a pressão de vapor de água, possuem uma relevância menor no nível de conforto térmico humano relativamente à situação de referência e gama de valores estudada, em comparação com outros parâmetros, tais como, o nível de metabolismo, vestuário, temperatura do ar e temperatura média radiante. Comparando as normas Europeias e a Americana os resultados obtidos para os índices de conforto térmico são semelhantes e as diferenças encontradas entre eles são residuais. Due to increased quality of life especially in developed countries, the thermal comfort has been required a growing concern over the years especially in terms of energy efficiency studies in order to reduce energy consumption without lowering the comfort level of the occupants. The level of thermal comfort is a citizen’s right, which may be required allowing a well-being in terms of health, productivity and longevity. The thermal comfort inside buildings depends on several parameters including: metabolic rate, clothing, air temperature, radiant temperature, air velocity and water vapor pressure. This master thesis aim to study the sensitivity analysis of the thermal comfort index PMV-PPD through a parametric study, making a change of the parameters that influence thermal comfort mentioned above. The study was conducted through a worksheet that is based on the methodology developed by Fanger and proposed in the ISO 7730 standard, as well as an American software that allows to make a comparison between the standards ASHRAE-55 and EN-15251. Taking into account the results obtained, it can be observed that parameters such as the air velocity and the water vapor pressure have a lower importance on human thermal comfort relative to the reference situation and the range of values studied in comparison with other parameters such as the level of metabolism, clothing, air temperature and mean radiant temperature. Comparing the European and the American standards the results obtained for the thermal comfort indexes are very similar and the differences between them are only residual. |
Description: | Dissertação de Mestrado em Engenharia Civil na especialidade de Construções, apresentada à Faculdade de Ciências e Tecnologia da Universidade de Coimbra. | URI: | https://hdl.handle.net/10316/97215 | Rights: | embargoedAccess |
Appears in Collections: | UC - Dissertações de Mestrado FCTUC Eng.Civil - Teses de Mestrado |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
Tese_PaulaForno_Versão_Final.pdf | 3.44 MB | Adobe PDF | View/Open |
Page view(s)
164
checked on Oct 29, 2024
Download(s)
300
checked on Oct 29, 2024
Google ScholarTM
Check
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.